P41-Ramp Soak Controllers- 96x96mm

Total 9 profiles, a profile with 16, 32 or 64 segments;
Each segment to be configured as a ramp or dwell(soak);
Fast A-D sampling rate (5 times/s);
High accuracy of 18-bit A to D input, and 15-bit D to A output;
The fast sample rate of 200 msec.

More details

New product
 
More info

The Fuzzy Logic plus PID microprocessor-based profiling controller with many segments of ramp and dwell, incorporate two bright, easy to read 4-digit LED displays, indicating process value and set point value. The Fuzzy Logic technology enables a process to reach a predetermined set point in the shortest time, with the minimum of overshoot during power-up or external load disturbance. 

As a professional and experienced manufacturer, we supply high-performance and quality ramp soak controllers, which is also called programmable temperature controllers.

Features
  • Total 9 profiles, a profile with 16, 32 or 64 segments at most
  • Each segment to be configured as a ramp or dwell(soak)
  • Fast A-D sampling rate (5 times/s)
  • After an event the process goes to run, hold, abort, manual, failure transfer, off mode, next segment or select the second PID values
  • High accuracy of 18-bit A to D input, and 15-bit D to A output
  • The fast sample rate of 200 msec
  • Fuzzy control to reach set point at the least overshooting ans less time
  • Up to three relays are configurable for event output
  • Analog retransmission of process value & set point value
  • Optional RS-485 or 232 communications
  • Programmable port for easy configuration or calibration
  • Lockout protection for security requirement
  • Bumpless transfer of safely control while sensor breaks
  • Digital filter to improve the stability of process value
  • SEL function for easy operation

Specification:

Power
90 - 250 VAC, 47 - 63 Hz, 12VA, 5W maximum
11 - 26 VAC / VDC, SELV, Limited Energy, 12VA, 5W maximum
Signal Input
Resolution18 bits
Sampling Rate5 times / second
Maximum Rating-2 VDC minimum, 12 VDC maximum( 1 minute for mA input )
Temperature Effect±1.5 uV/ °C for all inputs except mA input 
±3.0 uV/ °C for mA input
Sensor Lead Resistance EffectT/C: 0.2uV/ohm 
3-wire RTD: 2.6 °C/ohm of resistance difference of two leads 
2-wire RTD: 2.6 °C/ohm of resistance sum of two leads
Burn-out Current200nA
Common Mode Rejection Ratio ( CMRR )120dB
Normal Mode Rejection Ratio ( NMRR )55dB
Sensor Break DetectionSensor open for TC, RTD and mV inputs, 
Sensor short for RTD input, 
below 1 mA for 4-20 mA input, 
below 0.25V for 1 - 5 V input, unavailable for other inputs.
Sensor Break Responding TimeWithin 4 seconds for TC, RTD and mV inputs, 
0.1 second for 4-20 mA and 1 - 5 V inputs.
Input
TypeRange Accuracy@ 25 °CInput Impedance
J-120 ~ 1000 °C (-184 ~ 1832 °F)±2 °C2.2MΩ
K-200 ~ 1370 °C (-328 ~ 2498°F)±2 °C2.2MΩ
T-250 ~ 400°C (-418 ~ 752°F)±2 °C2.2MΩ
E-100 ~ 900 °C (-148 ~ 1652 °F)±2 °C2.2MΩ
B0 ~ 1800 °C (32 ~ 3272 °F)±2 °C (200°C - 1800°C)2.2MΩ
R0 ~ 1767.8 °C (32 ~ 3214 °F)±2 °C2.2MΩ
S0 ~ 1767.8 °C (32 ~ 3214 °F)±2 °C2.2MΩ
N-250 ~ 1300 °C (-418 ~ 2372 °F)±2 °C2.2MΩ
L-200 ~ 900 °C (-328 ~ 1652 °F)±2 °C2.2MΩ
PT100 (DIN)-210 ~ 700 °C (-346 ~ 1292 °F)±0.4°C1.3KΩ
PT100 (JIS)-200 ~ 600 °C (-328 ~ 1112 °F)±0.4°C1.3KΩ
mV-8 ~ 70mV±0.05%2.2MΩ
mA-3 ~ 27mA±0.05%70.5Ω
V-1.3 ~ 11.5V±0.05%650KΩ
Output 1 / Output 2
Relay Rating2A/240 VAC, life cycles 200,000 for resistive load
Pulsed VoltageSource Voltage 5V, current limiting resistance 66Ω .
Output
TypeZero ToleranceSpan ToleranceLoad Capacity
4-20 mA3.6-4 mA20-21 mA500Ω max.
0-20 mA0 mA20-21 mA500Ω max.
0-5 V0 V5-5.25 V10KΩ min.
1-5 V0.9-1 V5-5.25 V10KΩ min.
0-10 V0 V10-10.5 V10KΩ min.
Linear Output
Resolution15 bits
Output Regulation0.02 % for full load change
Output Settling Time0.1 sec. ( stable to 99.9 % )
Isolation Breakdown Voltage1000 VAC
Temperature Effect±0.01 % of SPAN / °C
Triac ( SSR ) Output
Rating1A / 240 VAC
Inrush Current20A for a cycle
Min. Load Current50 mA rms
Max. Off-state Leakage3 mA rms
Max. On-state Voltage1.5V rms
Insulation Resistance1000 Mohms min. at 500 VDC
Dielectric Strength2500 VAC for 1 minute
TypeToleranceMax. Output CurrentRipple VoltageIsolation Brrifer
20V±1V25mA0.2Vp-p500VAC
12V±0.6V40mA0.1Vp-p500VAC
5V±0.25V80mA0.05Vp-p500VAC
Alarm
Alarm RelayForm C,Max. rating 2A/240VAC, life cycles 200,000 for resistive load.
Alarm FunctionsDwell timer, 
Deviation High / Low Alarm, 
Deviation Band High / Low Alarm 
PV High / Low Alarm
Alarm ModeNormal, Latching, Hold, Latching / Hold.
Dwell Timer0.1 - 4553.6 minutes
Data Communication
InterfaceRS-232 ( 1 unit ), RS-485 ( up to 247 units )
ProtocolModbus Protocol RTU mode
Address1 - 247
Baud Rate2.4 ~ 38.4 Kbits/秒
Parity BitNone, Even or Odd
Stop Bit1 or 2 bits
Communication Buffer64 bytes
Analog Retransmission
Output Signal4-20 mA, 0-20 mA, 0-1V, 0-5V, 1-5V, 0-10V
Resolution15 bits
Accuracy±0.05 % of span ±0.0025 %/ °C
Load Resistance0 - 500 ohms ( for current output ),10 K ohm minimum ( for voltage output )
Output Regulation0.01 % for full load change
Output Settling Time0.1 sec. (stable to 99.9 % )
Isolation Breakdown Voltage1000 VAC min.
Integral Linearity Error±0.005 % of span
Temperature Effect±0.0025 % of span/ °C
Saturation Low0 mA ( or 0V )
Saturation High22.2 mA ( or 5.55V, 11.1V min. )
Linear Output Range0 - 22.2mA(0-20mA or 4-20mA), 
0 - 5.55V ( 0 - 5V, 1 - 5V ), 
0 - 11.1 V ( 0 - 10V )
User InterfaceDual 4-digit LED Displays
Keypad4 keys
Programming PortFor automatic setup, calibration and testing
Communication PortRS-232 and RS-485
Control Mode
Output 1Reverse ( heating ) or direct ( cooling )action
Output 2PID cooling control, cooling P band 50 ~ 300% of PB, dead band -36.0 ~ 36.0% of PB
ON-OFF0.1 - 90.0 ( °F ) hysteresis control ( P band = 0 )
P or PD0 - 100.0 % offset adjustment
PIDFuzzy logic modified , Proportional band 0.1 ~ 900.0°F , Integral time 0 - 1000 seconds , Derivative time 0 - 360.0 seconds
Cycle Time0.1 - 90.0 seconds
Manual ControlHeat (MV1) and Cool (MV2)
Auto-tuningCold start and warm start
Failure ModeAuto-transfer to manual mode while sensor break or A-D converter damage
Ramping Control0 ~ 900.0°F/minute or 0 ~ 900.0 °F/hour ramp rate
Digital Filter
FunctionFirst order
Time Constant0, 0.2, 0.5, 1, 2, 5, 10, 20, 30, 60 seconds programmable
Profiler
Number of profiles9
Number of Segment per profileProfile 1,2,3,4 : 16 
Profile 5,6,7 : 32 
Profile 8,9 : 64
Event Outputs3
Environmental & Physical
Operating Temperature-10°C ~ 50°C
Storage Temperature-40°C ~ 60°C
Humidity0 to 90 % RH ( non-condensing )
Altitude2000m maximum
PollutionDegree 2
Insulation Resistance20 Mohms min. ( at 500 VDC )
Dielectric Strength2000 VAC, 50/60 Hz for 1 minute
Vibration Resistance10 - 55 Hz, 10 m/s² for 2 hours
Shock Resistance200 m/s² ( 20 g )
MoldingsFlame retardant polycarbonate
DimensionsP41 ---96mm(W) X 96mm(H) X 65mm(D), 53 mm depth behind panel 
P91 ---48mm(W) X 48mm(H) X 116mm(D), 105 mm depth behind panel
WeightP41 --- 250 grams 
P91 --- 150 grams
Approval StandardsSafety : UL 61010C-1 , CSA C22.2 No. 24-93 , 
EN61010-1 (IEC1010-1)

Application:

  • Plastic/rubber industry
  • Electric heating furnace industry
  • Vacuum furnace equipment / vacuum melting / vacuum heat treatment
  • Semiconductor industry
  • Ceramic / kiln / glass industry
  • Fiber machinery
 
Tags

Contact Us

“Industrial Technical Services is a single source Instrumentation and Automation company. We provide certified calibrations, PLC programming, custom controls and Panels”.

 

Please fill details below and one of our representative will contact you shortly. 

30 other products in the same category: