ABM Series Simple and reliable non-contact level measurement of fluids

ABM Series Simple and reliable non-contact level measurement of fluids

More details

Online only
New product
 
More info

The Babbitt ABM Series Ultrasonic Level Transmitter allows simple and reliable non-contact level measurement of fluids in a tank, sump or other container. The microprocessor-controlled circuit generates a pulse that is transmitted from the transducer face. This pulse is reflected back from the surface of the liquid. The "round trip" transit time is then converted into the current output, which is directly proportional to the fluid level.

The circuit automatically filters out false echoes that may be produced by peripheral obstructions in the tank. For example, a pipe or ladder that is in the "ultrasonic cone" (but not directly in front of the transducer's face) will be ignored; the ABM Series has a proprietary circuit that locks onto the farthest echo which will always be the fluid level. 

Features

  • Simple push-button calibration
  • Ignores peripheral obstructions
  • 4-20mA or 20-4mA output
  • Microprocessor-based reliability
  • Built-in temperature compensation
  • Current loop diagnostics
  • Field or bench calibration

Applications

  • Water/Wastewater
  • Chemicals
  • Viscous Fluids
  • Oils
  • Slurries
  • Food and Beverage

 

The current output (4-20mA) can power a load of up to 750 ohms. The power source for the current loop is field selectable via an on-board jumper; the ABM Series can provide the power for the loop or an external 24VDC power supply may be used.


The Factory can supply digital readouts with optional setpoints for self-contained alarm/control systems.

A single push-button is used to set the point for 4mA and 20mA. The output may be either proportional (elevation) (4-20mA with zero=4mA at the bottom of the tank) or inversely proportional (depth) (20-4mA with 4mA=zero at the top of the tank). 

The 4mA and 20mA points are independent and fully adjustable over the span of the unit. Feedback for the calibration procedure is provided via a "green-yellow-red" LED.

The calibration settings are stored in non-volatile memory, so the unit stays calibrated even during loss of power.

 
Specifications
Electrical: Power (+/- 20%) 115VAC/60Hz
230VAC/50Hz (Optional)
12-30VDC
  Output 4-20mA or 20-4mA
6.12uA resolution
750 Ohms
Isolated with AC supply
Non-isolated with DC supply
  Fuse 0.125A/250V type 2AG
Mechanical: Process Entry Threaded per chart
  Conduit Entry 1/2" NPT Plastic Conduit
  Transducer: PVC
  Enclosure: PVC-94V0
Environmental: Temperature: -40F to 140F (transducer and electronics)
  Pressure: 15 PSIG Max.
  Area: ENTELA Certified #8294
CSA1010.1
UL 61010A-1
IEC 61010
Operational: Dead Zone / Range: Model dependent (see chart on PDF)
  Accuracy: +/-0.25 of span
  Lost Echo Hold Time: 30 Seconds
Output 22mA
  Temperature Compensation: In transducer

Specifications are subject to change without notice.

Contact Us

“Industrial Technical Services is a single source Instrumentation and Automation company. We provide certified calibrations, PLC programming, custom controls and Panels”.

 

Please fill details below and one of our representative will contact you shortly. 

21 other products in the same category: