H5 Electronic humidity, temperature and dew point transmitter

New product
 
More info

Features

  • Wall, duct mount or remote sensor relative humidity electronic transmitter
  • With replaceable "Humy-chip" capacitive sensor and filters
  • Voltage, Current or PT100 output according to the selected signal and model
  • Alarm digital output
  • Reading, calculation and display of several variables:
    • Relative humidity (RH)
    • Temperature (T)
    • Dew Point (DP)
    • Temperature difference between T and DP (ΔT)
  • Data and event logging
  • RS 485 port with ModBus RTU protocol (optional)
  • LCD Display (optional)
 
Specifications

Process inputs:

“Humy Chip” for temperature and Humidity acquisition

Self calibrating

2 reciprocally insulated outputs:

Available Output signals:

- Voltage (V): 0...10 V, 0...1V
Min. impedence 500Ω
- Current (mA): 0/4...20 mA
Max. impedence 500Ω
- 3 wire PT100 accuracy class B (1/2 DIN)
Any of the two outputs may be configured for Humidity, temperature, ΔT and Dew point

Selectable outputs:

Humidity :
Accuracy: 1.8% between 10... 90% RH
Range: 0... 100% RH
Long term drift: typically <0.5% RH/year
Temperature 
Accuracy <0.5°C between 0… +50°C (32... 122°F)
Available ranges:
-30.0… +70.0°C (-22... 158°F)
-20.0… +30.0°C (-4... 86°F)
0.0… +50.0°C (32... 122°F)
0.0… +100.0°C (32... 212°F)
Dew Point (DP)
Accuracy <1°C between 30... 100% RH and -20... +90°C (-4... +164°F)
Available ranges:
-30.0… +70.0°C (-22... 158°F)
0.0… +100.0°C (32... 212°F)
Other ranges on request in °C or °F
ΔT (between T and DP)
Available range: 0.0... 50.0°C (32... 122°F)

Digital Output for alarm

- 1 Relay SPST-NO 1A (30 V)

Power supply:

- With (mA) output: 10... 30 Vdc
- With (V) outputs:  18... 27 Vac or 20... 30 Vdc

Functions:

Humidity and temperature retransmission

- Dew point calculation
- ΔT calculation (as difference between actual temperature and dew point)
- Up to 5 alarms freely configurable to the relay output
- Data and event logging

Communication and programming:

Interfaces

- RS 485 port with ModBus RTU and J-bus (slave) protocols (optional)

Programming/configuration tools:

- Configuration software available for PC

Installation:

Mounting method:
- Wall mount
- Duct mount
- Remote sensor
Case dimensions: 100 x 100 x 61 mm
Cable gland : 35 mm max.
Cable probe connector: 25 mm
Protection filter:
- Wire mesh
- Sintered stainless steel
- Teflon
Protects against dust and other atmospheric contaminants.

Display and indicators

LCD Display (optional) size 3.65 mm,3 Digits 16 characters

Connectable to:

- Any controller from Ascon Tecnologic range with the appropriate I/Os
- SCADA for monitoring, traceability and remote management
- DX and DY gateways for remote monitoring

Contact Us

“Industrial Technical Services is a single source Instrumentation and Automation company. We provide certified calibrations, PLC programming, custom controls and Panels”.

 

Please fill details below and one of our representative will contact you shortly. 

30 other products in the same category: