New Product
Ozone (Ambient) / Chemical & Petrochemical / Pharma / Water & Waste Water
Model 205 Dual Beam Ozone Monitor High
Ozone (Industrial) / Chemical & Petrochemical / Pharma / Water & Waste Water
106-MH Ozone MonitorTM (Industrial)
Ozone (Industrial) / Automotive & Manufacturing / Chemical & Petrochemical / Dairy / Food & Beverage / Lab & Gas / Pharma / Plastics / Power & Steam
106-HIndustrial Ozone MonitorTM
LS8000/2 Foam Detection Sensor (Remote Mount Electronics)
Features
- Field selectable Auto Fill or Auto Empty;
- 10 Amp latching relay for pump control;
- Solid state, no moving parts;
- Simple installation and calibration.
Downloads
The LS8000/2 dual-point level switch can measure virtually any liquid, dry material (2 probe configuration) or interface of electrically conductive or non-conductive products. The proprietary radio frequency (RF) balanced impedance bridge has exceptional temperature stability, thus eliminating the need to recalibrate the unit from season to season. The LS8000 can be configured for single-point, dual-point or four-point control. The maintenance-free transmitter is mounted in the explosion-proof head of the probe. The receiver can be mounted up to one mile from the transmitter.
Overview
The LS8000/2 Dual Point is designed to be used with homogeneous fluids when configured for multiple set points on one probe. A coated probe is required for liquids with a dielectric constant greater than 12.
The LS8000/2 is specifically designed to automatically fill or empty a tank, hopper or sump. The high and low set points are adjustable over the entire length of the probe. Each receiver has 3 SPDT relay outputs. One is a latching relay for field-selectable “AUTO-FILL” or “AUTO-EMPTY” control. The other two relays provide high and low set point outputs.
The probe is made of a HALAR coated 316 Stainless Steel rod, 3/4″ NPT process connection and the insulator is made of Teflon. The standard coating is HALAR, but other options such as a Teflon Sleeve are available. The seals are made with Viton “O” rings. The transmitter electronics are housed in a cast aluminum explosion-proof enclosure. The receiver board is provided with a snap-track mounting or can be purchased with an optional enclosure.

Features
- Field selectable Auto Fill or Auto Empty
- 10 Amp latching relay for pump control
- Solid state, no moving parts
- Simple installation and calibration
- Explosion proof housing standard
- On-board fuse protection
- User Programmable time delay
- Modular electronics easily replaced
Applications
- Auto Fill/Auto Empty
- Pump control
- High/Low level alarm
Liquids:
- Water
- Acids/Caustics
- Fuels/Oils
- Solvents
Solids (Dual Point Configuration Only):
- Plastic pellets
- Sands
- Cement
- Flours
- Powders

Industrial Technical Services from Mississauga; Ontario is a single source Instrumentation and Automation company. We provide certified calibrations, PLC programming, custom controls and Panels.
Specifications & Spare Parts
|
||||||||||||||||||||||||
|
Specifications are subject to change without notice. |



