New Product
Ozone (Ambient) / Chemical & Petrochemical / Pharma / Water & Waste Water
Model 205 Dual Beam Ozone Monitor High
Ozone (Industrial) / Chemical & Petrochemical / Pharma / Water & Waste Water
106-MH Ozone MonitorTM (Industrial)
Ozone (Industrial) / Automotive & Manufacturing / Chemical & Petrochemical / Dairy / Food & Beverage / Lab & Gas / Pharma / Plastics / Power & Steam
106-HIndustrial Ozone MonitorTM
PD540 Digital temperature controller with auto-tuning PID capabilities
The Nova PD540 is a digital temperature controller with auto-tuning PID capabilities that is available in 1/16, 3/16, 1/8, and 1/4 DIN sizes. Models include standard one-directional control (i.e. heating or cooling) or bi-directional heating and cooling control. One of four user programmable set points may be selected for PID control in the form of time proportional relay on/off output, time proportional voltage pulse output, or 4-20 mA signal control. Its universal input accepts 23 input varieties, including thermocouple, RTD, and voltage inputs, and it can be easily configured for a 4-20 mA input. It is available with up to three (3) relays, two (2) 4-20 mA analog outputs, two (2) digital inputs, and an RS485 serial communication option which includes protocols for master/slave set point control, Modbus® ASCII and RTU, as well as PC software.
Features
- Thermocouple, RTD, & Process Inputs
- High Accuracy Auto-Tuning PID
- Heating & Cooling Models
- Universal Power Supply 100-240 VAC
- Up to 3 Relays & 2 Analog Outputs
- Digital Input Set Point Selection
- RS-485 Serial Communications Option
- Modbus® RTU/ASCII Communications
- Free Operating & Data Logging Software
- IP55 & IP65 Fronts
- 1/16, 3/16, 1/8, 1/4 DIN Sizes
- 3 Year Warranty
Specifications & Spare Parts
General
| Display | Dual 4 digits, red LED, -1999 to 9999 | ||||||||||||||||||||||||
|
|||||||||||||||||||||||||
| Front Panel | Panel gasket provided. 1/16 & 1/8 DIN: IP65, 3/16 & 1/4 DIN: IP55 | ||||||||||||||||||||||||
| Programming Methods | Four front panel buttons and Modbus | ||||||||||||||||||||||||
| Number of Set Points | Four programmable set points | ||||||||||||||||||||||||
| Noise Filter | Programmable 1 to 120 seconds or off | ||||||||||||||||||||||||
| Display Update Rate | 4/second | ||||||||||||||||||||||||
| Password | Restricts modification of programmed settings. | ||||||||||||||||||||||||
| Non-Volatile Memory | Settings stored for a minimum of 10 years | ||||||||||||||||||||||||
| Power | 100-240 VAC, 50/60 Hz, 10 W | ||||||||||||||||||||||||
| Required Fuse | UL Recognized, 1 A, 250 V, slow-blow | ||||||||||||||||||||||||
| Isolation | 2300 V input/output-to-power line; 4 kV relay output-to-input/output/power line. | ||||||||||||||||||||||||
| Operating Temperature | 10 to 50°C | ||||||||||||||||||||||||
| Storage Temperature | -40 to 85°C | ||||||||||||||||||||||||
| Relative Humidity | 20 to 90% non-condensing | ||||||||||||||||||||||||
| Enclosure | 1/16, 3/16, 1/8(H), 1/8(V), 1/4 DIN; impact-resistant plastic; color: black | ||||||||||||||||||||||||
| Approvals | UL & C-UL Recognized, CE Compliant | ||||||||||||||||||||||||
| UL File Number | E244207; Process Control Equipment | ||||||||||||||||||||||||
| Warranty | 3 years parts & labor | ||||||||||||||||||||||||
Temperature Inputs
| Inputs | Factory calibrated, field selectable: J, K, T, E, B, R, S, L, U, N, W, Platinel II thermocouples, and 100 Ω platinum RTD (0.00385 or 0.00392 curve) |
| Cold Junction Reference | Automatic or off |
| Offset Adjustment | Four programmable input bias zones |
| Sensor Break | User selectable; display reads S.OPN; alarm relays follow the up or down scale selection. |
| Type | Range (°C) | Range (°F) | Accuracy |
| Thermocouple Inputs | |||
| K1 | -200 to 1370 | -300 to 2500 | >0ºC: ± 0.1% FS ± 1 count <0ºC: ± 0.2% FS ± 1 count |
| K2 | -199.9 to 999.9 | 0 to 2300 | |
| J | -199.9 to 999.9 | -300 to 2300 | |
| T | -199.9 to 400.0 | -300 to 750 | |
| E | -199.9 to 999.9 | -300 to 1800 | |
| B | 0 to 1800 | 32 to 3300 | >400ºC: ± 0.15% FS ± 1 count <400 ºC: ± 5% FS ± 1 count |
| R | 0 to 1700 | 32 to 3100 | ±0.15% FS ± 1 count |
| S | 0 to 1700 | 32 to 3100 | |
| L | -199.9 to 900.0 | -300 to 1600 | >0ºC: ± 0.1% FS ± 1 count <0ºC: ± 0.2% FS ± 1 count |
| U | -199.9 to 400.0 | -300 to 750 | |
| N | -200 to 1300 | -300 to 2400 | >0ºC: ± 0.1% FS ± 1 count <0ºC: ± 0.25% FS ± 1 count |
| W | 0 to 2300 | 32 to 4200 | ±0.2% FS ± 1 count |
| Platinel II | 0 to 1390 | 32 to 2500 | ±0.1% FS ± 1 count |
| RTD Inputs | |||
| PtA | -199.9 to 850.0 | -300 to 1560 | ±0.1% FS ± 1 count |
| PtB | -199.9 to 500.0 | -199.9 to 999.9 | |
| PtC | -19.99 to 99.99 | -4.0 to 212.0 | ±0.2% FS ± 1 count |
| JPtA | -199.9 to 500.0 | -199.9 to 999.9 | ±0.1% FS ± 1 count |
| JPtB | -150.0 to 150.0 | -199.9 to 300 | |
*Performance within recommended operating conditions (10 to 50 ºC, 20 to 90% RH)
Process Inputs
| Inputs | Field selectable: 0.4 to 2.0 V, 1 to 5 V, 0 to 10 V, -10 to 20 mV, 0 to 100 mV. 4-20 mA input requires 100 Ω resistor connected across input terminals (order P/N: PDX-RES1). |
| Accuracy | ±0.1% FS ±1 count |
| Decimal Point | Up to 3 decimals: 9.999, 99.99, 999.9 or 9999 |
| Calibration | All inputs are calibrated at the factory |
| Scale Range | User programmable over entire range |
| Transmitter Supply | 14 to 18 VDC @ 20 mA; available at terminals OUT2 or OUT3, instead of retransmitting analog output; selection through front panel. |
Relays
| Ratings | 1 Form C (SPDT) standard; rated 3 A @ 30 VDC or 3 A @ 250 VAC resistive load. 1 or 2 Form A (SPST) optional; rated 1 A @ 30 VDC or 1 A @ 250 VAC resistive load. |
| Relay Operation | Time proportional PID control, on/off control, forward or reverse (fail-safe) alarm, or run status |
| Cycle Time | 1 to 300 seconds; time proportional PID control only |
| On/Off Hysteresis | 0-10.0% of sensor range for independent high and low hysteresis limit. For heating & cooling models, 0-10.0% of sensor range full hysteresis band. |
| High/Low Alarm | User may program any alarm for absolute high or low trigger values. |
| Deviation Alarm | User may program any relay for high, low, or high/low range set point deviation alarm. |
| Alarm Deadband | 0-100% FS, user selectable |
| Alarm Delay | 0 to 99 minutes and 59 seconds |
| Reverse Operation (Fail-Safe) | Programmable, independent for each alarm. Relay coils are energized in non-alarm condition. In case of power failure, relays will go to alarm state. |
| Forward Operation | Relay coils are energized in alarm condition. In case of power failure, relays will go to non-alarm state. |
| Auto Alarm Initialization | Normal and standby operation independent for each alarm. Standby alarms will not trigger if the change to alarm state is a result of power up cycle, set point change, or alarm configuration change. |
| Run Status | Relays will energize when PID outputs are running. |
Analog Outputs
| Scaling Range | Retransmitting 4-20 mA outputs can be scaled for any display range. |
| Accuracy | ±0.1% FS |
| Availability | 1/16 & 3/16 DIN: 1 standard, 1 optional 1/8 & 1/4 DIN: 2 standard |
| Output Operation | 4-20 mA PID control, time proportional voltage pulse PID control, or 4-20 mA retransmitting |
| Ratings | Continuous 4-20 mA PID or retransmitting: 600 Ω max Time Proportional PID: 15 VDC pulse high, less than 0.1 VDC pulse low; 600 Ω minimum, current limited at 30 mA |
| Cycle Time | 1 to 300 seconds; time proportional PID control only |
| Power | Internally powered 4-20 mA output |
| Isolation | 500 V input-to-output |
| Output Loop Resistance | 600 Ω max |
Digital Inputs
| Configuration | Two contacts, two operating modes |
| Contacts | Normally open switches (external excitation not required) or open collector transistor |
| Open Circuit Voltage | Approximately 5 VDC |
| Logic Levels | LO = 0 to 0.8 VDC, HI = 4.7 to 28 VDC |
| Operation Modes | Mode 1: Control output run or stop, selection of set point 1 or 2. Mode 2: Selection of set points 1 to 4. |
Serial Communications
| Compatibility | EIA-485 |
| Protocol | PC, Modbus (ASCII, RTU), Sync (Master/Slave SP Control) |
| Address | 1 to 99 (Max 31 units connected) |
| Baud Rate | 600 to 19,200 bps |
| Transmit Time Delay | 0 to 100 ms |
| Data | 7 or 8 bit, automatic when using Modbus protocol |
| Stop Bit | 1 or 2 |
| Parity | None, even, or odd |