PD8-6262 ProtEx MAX Explosion-Proof Dual Analog Input Flow

Get a quote

The ProtEX-MAX™ PD8-6262 offers all the functionality of the ProVu PD6262 as a fully FM, CSA, ATEX, and IECEx approved explosion-proof product. It is specifically designed to display flow rate and total from two (2) analog output (4-20 mA, 0-5 V, 1-5 V, etc.) flowmeters. It displays these signals on a dual-line, 6-digit Sunbright sunlight readable display. The two display lines can be used to show both flow rates simultaneously, to alternate between the two inputs showing both the flow rate and total of each, or to show the result of math functions performed on the flow rates and totals. The total overflow feature allows up to 9-digit totals and grand totals to be displayed. The PD8-6262 includes a 24 VDC power supply to drive the flowmeter and can be equipped with up to four internal relays and a 4-20 mA analog output. It can be programmed and operated without opening the housing by using the built-in SafeTouch® through-glass buttons or the RS485 serial communication port with free Modbus® protocol.

Quick Overview

  • Input: Two analog inputs, each separately field selectable; 0-20 mA, 4-20 mA; ±10 VDC
    (0-5, 1-5, 0-10 V); Modbus PV (slave)
  • Display: Dual-line 6-digit, 0.60″ (15 mm) & 0.46″ (12 mm)
  • Case: Smooth die-cast aluminum explosion-proof
  • Power: 85-265 VAC or 12-24 VDC option
  • Operating Temperature: -40 to 65°C

Features

  • SunBright Display Standard
  • Rate, Total, and Grand Total for Each Input Channel
  • Addition, difference, absolute difference, average, multiplication, division, min of A or B, max of A or B, draw, weighted average, and ratio math functions including total and grand total math
  • Isolated 24 VDC @ 25 mA transmitter power supply
  • 32-point linearization with free software
  • Total, grand total, or non-resettable grand total
  • SafeTouch® through-glass button programming
  • Modbus RS-485 serial communications
  • Flanges for wall or pipe mounting
  • Isolated 24 VDC @ 25 mA transmitter power supply
  • Onboard USB and MeterView® Pro programming software

Specifications & Spare Parts

Display Upper display: 0.60″ (15 mm) high. Lower display: 0.46″ (12 mm) high. 6 digits each (-99999 to 999999), red LEDs with lead zero blanking.
Display Intensity Eight user selectable intensity levels
Display Update Rate 5/second (200 ms)
Overrange Display flashes 999999
Underrange Display flashes -99999
Display Assignment The Upper and Lower displays may be assigned to show: One or more rate channels: Channel A (Ch-A), B (Ch-B), or C (Ch-C), Toggle between rate channels: Ch-A & Ch-B, Ch-A & Ch-C, Ch-B & Ch-C, and Ch-A, Ch-B, & Ch-C, Total or grand total: Ch-A or Ch-B, Rate and total or grand total: Ch-A, Ch-B, Relay set points, Max and/or min values: Ch-A, Ch-B, or Ch-C, Toggle between any rate channel & units, Toggle between any rate/math channel & units, Total and units: Ch-A or Ch-B, Toggle between totals: Ch-A & Ch-B; Ch-A, Ch-B, and sum of Ch-A and Ch-B, Modbus input. The lower display may also be set to show engineering units or be off, with no display.
Programming Methods Four through-glass SafeTouch buttons, four mechanical buttons behind glass, digital inputs, PC and MeterView Pro software, or Modbus registers.
F4 Digital Input Contacts 3.3 VDC on contact. Connect normally open contacts across F4 to COM.
Max/Min Display Max/min readings reached by the process are stored until reset by the user or until power to the meter is cycled.
Password Three programmable passwords restrict modification of programmed settings and two prevent resetting the totals. Pass 1: Allows use of function keys and digital inputs, Pass 2: Allows use of function keys, digital inputs and editing set/reset points, Pass 3: Restricts all programming, function keys, and digital inputs. Total: Prevents resetting the total manually Gtotal: Prevents resetting the grand total manually.
Noise Filter Programmable from 2 to 199 (0 will disable filter)
Non-Volatile Memory All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
Recalibration All ranges are calibrated at the factory. Recalibration is recommended at least every 12 months.
Power Options 85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max, or optional model with 12-24 VDC ±10%, 15 W max.
Fuse Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse.
Isolated Transmitter Power Supply Terminals P+ & P-: 24 VDC ± 10%. Isolated from the input at >500 V. Jumper selectable for 24, 10, or 5 VDC supply (internal jumper J4). All models transmitter supply rated @ 25mA max.
Normal Rejection Mode Greater than 60 dB at 50/60 Hz
Isolation 4 kV input/output-to-power line. 500 V input-to-output or output-to-P+ supply.
Overvoltage Category Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
Environmental T6 Class operating temperature range Ta = -40 to 60°C, T5 Class operating temperature range Ta = -40 to 65°C
Max Power Dissipation Maximum power dissipation limited to 15.1 W.
Connections Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters.
Enclosure Explosion-proof die cast aluminum with glass window, corrosion resistant epoxy coating, color: blue. NEMA 4X, 7, & 9, IP68. Default conduit connections: Four ¾” NPT threaded conduit openings and two ¾” NPT metal conduit plugs with 12 mm hex key fitting installed. Additional conduit opening configurations may be available; verify quantity and sizes on specific device labeling during installation.
Mounting Four slotted flanges for wall mounting or NPS 1½” to 2½” or DN 40 to 65 mm pipe mounting
Dimensions 6.42″ x 7.97″ x 8.47″ (W x H x D) (163 mm x 202 mm x 215 mm)
Weight 16.0 lbs (7.26 kg)
Warranty 3 years parts & labor
USB Connection Compatibility: USB 2.0 Standard, Compliant. Connector Type: Micro-B receptacle. Cable: USB A Male to Micro-B Cable. Driver: Windows 98/SE, ME, 2000, Server 2003/2008, XP 32/64-Bit, Vista 32/64-Bit, Windows 7 32/64-Bit, Windows 10 32/64-Bit. Power: USB Port.
Accuracy ±0.03% of calibrated span ±1 count
Temperature Drift 0.005% of calibrated span/°C max from 0 to 65°C ambient, 0.01% of calibrated span/°C max from -40 to 07°C ambient
Input Impedance Voltage ranges: greater than 500 KΩ. Current ranges: 50 – 100 Ω (depending on resettable fuse impedance)
Input Overload Current input protected by resettable fuse, 30 VDC max. Fuse resets automatically after fault is removed.
Relay Ratings 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (≈ 50 W) @ 125/250 VAC for inductive loads
Dual Analog Output Expansion Module Two passive 4-20 mA analog outputs
Scaling Range 3.000 to 23.000 mA for any display range
Product Ratings and Approvals FM Enclosure: Type 4X; IP66 Class I, Division 1, Groups B, C, D Certificate Number: 3047283. CSA: Class I, Division 1, Groups B, C, D Certificate Number: 2531731. ATEX: II 2 G D, Certificate number: Sira 12ATEX1182. IECEx: Ex d IIC T* Gb, Certificate Number: IECEx SIR 12.0073