PD8-6200 ProtEX-MAX Explosion-Proof Analog Input Flow Rate/Totalizer

 

Get a quote

The ProtEX-MAX™ PD8-6200 offers all the functionality of the ProVu PD6200 as a fully FM, CSA, ATEX, and IECEx approved explosion-proof product. It is specifically designed to display flow rate and total from an analog output (4-20 mA, 0-5 V, 1-5 V, etc.) flowmeter. It displays that signal on a dual-line, 6-digit Sunbright sunlight readable display. Flow rate is typically displayed on the upper line and the cumulative total is displayed on the lower line. The total overflow feature allows up to a 9-digit total and grand total to be displayed. The PD8-6200 includes a 24 VDC power supply to drive the flowmeter and can be equipped with up to four internal relays and a 4-20 mA analog output. It can be programmed and operated without opening the housing by using the built-in SafeTouch® through-glass buttons or the RS485 serial communication port with free Modbus® protocol.

 

Quick Overview

  • Input: 0-20 mA, 4-20 mA; ±10 VDC (0-5, 1-5, 0-10 V); Modbus PV (slave)
  • Display: Dual-line 6-digit, 0.60″ (15 mm) & 0.46″ (12 mm)
  • Case: Smooth die-cast aluminum explosion-proof
  • Power: 85-265 VAC or 12-24 VDC option
  • Operating Temperature: -40 to 65°C

Specifications & Spare Parts

General
Display Upper display: 0.60″ (15 mm) high. Lower display: 0.46″ (12 mm) high. Both are 6 digits (-99999 to 999999), red LEDs.
Display Intensity Eight user-selectable intensity levels
Display Update Rate 5/second (200 ms)
Overrange Display flashes 999999
Underrange Display flashes -99999
Display Assignment The upper and lower displays may be assigned to rate, total, grand total, alternate (rate/total, rate/grand total, rate/units, total/units, and grand total/units), max/min, units (lower display only), set points, or Modbus input. Additional displays are available if the parameter total is off, and the parameter d-SCAL is on: gross, alternating gross/net, PV1, PV2, and PCT (refer to PD6000 instruction manual).
Programming Methods Four through-glass SafeTouch buttons, four mechanical buttons behind glass, digital inputs, PC and MeterView Pro software, or Modbus registers.
F4 Digital Input Contacts 3.3 VDC on contact. Connect normally open contacts across F4 to COM.
F4 Digital Input Logic Levels Logic High: 3 to 5 VDC; Logic Low: 0 to 1.25 VDC
Noise Filter Programmable from 2 to 199 (0 will disable filter)
Filter Bypass Programmable from 0.1 to 99.9% of calibrated span
Recalibration All ranges are calibrated at the factory. Recalibration is recommended at least every 12 months.
Max/Min Display Max (Peak) / min (Valley) readings reached by the process are stored until reset by the user or until power to the meter is cycled.
Password Three programmable passwords restrict modification of programmed settings and two prevent resetting the totals.
Non-Volatile Memory All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
Power Options 85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max, or optional model with 12-24 VDC ±10%, 15 W max.
Fuse Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse.
Isolated Transmitter Power Supply Terminals P+ & P-: 24 VDC ± 10%. Isolated from the input at >500 V. Jumper selectable for 24, 10, or 5 VDC supply (internal jumper J4). All models transmitter supply rated @ 25mA max.
Normal Rejection Mode Greater than 60 dB at 50/60 Hz
Isolation 4 kV input/output-to-power line. 500 V input-to-output or output-to-P+ supply.
Overvoltage Category Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
Environmental T6 Class operating temperature range Ta = -40 to 60°C; T5 Class operating temperature range Ta = -40 to 65°C
Max Power Dissipation Maximum power dissipation limited to 15.1 W.
Connections Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters.
Enclosure Explosion-proof die-cast aluminum with glass window, corrosion-resistant epoxy coating, color: blue. NEMA 4X, 7, & 9, IP68. Default conduit connections: Four ¾” NPT threaded conduit openings and two ¾” NPT metal conduit plugs with 12 mm hex key fitting installed. Additional conduit opening configurations may be available; verify quantity and sizes on specific device labeling during installation.
Mounting Four slotted flanges for wall mounting or NPS 1½” to 2½” or DN 40 to 65 mm pipe mounting
Dimensions 6.42″ x 7.97″ x 8.47″ (W x H x D) (163 mm x 202 mm x 215 mm)
Weight 16.0 lbs (7.26 kg)
Warranty 3 years parts & labor
USB Connection Compatibility: USB 2.0 Standard, Compliant; Connector Type: Micro-B receptacle; Cable: USB A Male to Micro-B Cable; Driver: Windows 98/SE, ME, 2000, Server 2003/2008, XP 32/64-Bit, Vista 32/64-Bit, Windows 7 32/64-Bit, Windows 10 32/64-Bit; Power: USB Port
Analog Inputs
Inputs Field selectable: 0-20, 4-20 mA, ±10 VDC (0-5, 1-5, 0-10 V), Modbus PV (Slave)
Accuracy ±0.03% of calibrated span ±1 count, square root & programmable exponent accuracy range: 10-100% of calibrated span
Temperature Drift 0.005% of calibrated span/°C max from 0 to 65°C ambient, 0.01% of calibrated span/°C max from -40 to 0°C ambient
Math Function Linear, square root, programmable exponent, or round horizontal tank volume calculation.
Multi-Point Linearization 2 to 32 points
Programmable Exponent 1.0001 to 2.9999
Low-Flow Cutoff 0-999999 (0 disables cutoff function)
Decimal Point Up to five decimal places or none: d.ddddd, dd.dddd, ddd.ddd, dddd.dd, ddddd.d, or dddddd.
Calibration Range
Input Range Minimum Span Input 1 & 2
4-20 mA 0.15 mA
±10 V 0.10 V
Input Impedance Voltage ranges: greater than 1 MΩ. Current ranges: 50 – 100 Ω (depending on resettable fuse impedance).
Input Overload Current input protected by resettable fuse, 30 VDC max. Fuse resets automatically after fault is removed.
Rate/Totalizer
Rate Display Indication 0 to 999999, lead zero blanking. “R” LED illuminates while displaying rate. Total Display & Total Overflow: 0 to 999,999; automatic lead zero blanking. “T” LED is illuminated while displaying total and “GT” for grand total. Up to 999,999,999 with total-overflow feature. “oF” is displayed to the left of total overflow and ▲ LED is illuminated.
Total Decimal Point Up to five decimal places or none: d.ddddd, dd.dddd, ddd.ddd, dddd.dd, ddddd.d, or dddddd. Total decimal point is independent of rate decimal point.
Totalizer Calculates total based on rate and field programmable multiplier to display total in engineering units. Time base must be selected according to the time units in which the rate is displayed. Selectable up/down count. Total Conversion Factor: 0.00001 to 59,999
Totalizer Rollover Totalizer rolls over when display exceeds 999,999,999. Relay status reflects the display value.
Total Overflow Override Program total reset for automatic with 0.1 second delay and set point 1 for 999,999
Totalizer Presets Up to eight, user-selectable under the Setup menu. Any set point can be assigned to total and may be programmed anywhere in the range of the meter for total alarm indication.
Programmable Total Reset Delay 0.1 to 999.9 seconds; applied to the first relay assigned to total or grand total. If the meter is programmed to reset total to zero automatically when the preset is reached, then a delay will occur before the total is reset.
Total Reset Via front panel button, external contact closure on digital inputs, automatically via user-selectable preset value and time delay, or through serial communications.
Total Reset Password Total and grand total passwords may be entered to prevent resetting the total or grand total from the front panel.
Non-Resettable Total The grand total can be programmed as a non-resettable total by entering the password “050873”. Caution: Once the Grand Total has been programmed as “non-resettable” the feature cannot be disabled.
Relays
Rating 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (≈ 50 W) @ 125/250 VAC for inductive loads
Noise Suppression Noise suppression is recommended for each relay contact switching inductive loads.
Relay Assignment Relays may be assigned to rate, total, or grand total.
Deadband 0-100% of span, user-programmable
High or Low Alarm User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turned off).
Relay Operation automatic (non-latching), latching (requires manual acknowledgment), sampling (based on time), pump alternation control (2 to 8 relays), off (disable unused relays), and manual on/off control mode.
Relay Reset User-selectable via front panel buttons, digital inputs, or PC:

  • Automatic reset only (non-latching), when input passes the reset point or total is reset to zero.
  • Automatic + manual reset at any time (non-latching).
  • Manual reset only, at any time (latching).
  • Manual reset only after alarm condition has cleared (latching).

Note: The front panel button or digital input may be assigned to acknowledge relays programmed for manual reset.

Time Delay 0 to 999.9 seconds, on & off relay time delays. Programmable and independent for each relay.
Fail-Safe Operation Programmable and independent for each relay.Note: Relay coil is energized in non-alarm condition. In case of power failure, the relay will go to alarm state.
Auto Initialization When power is applied to the meter, relays will reflect the state of the input to the meter.
Isolated 4-20 mA Transmitter Output
Output Source Rate/process, total, grand total, max, min, set points 1-8, manual control setting, or Modbus input
Scaling Range 1.000 to 23.000 mA for any display range
Calibration Factory calibrated: 4.000 to 20.000 = 4-20 mA output
Analog Output Programming 23.000 mA maximum for all parameters: Overrange, underrange, max, min, and break
Accuracy ±0.1% FS ±0.004 mA
Temperature Drift 0.4 µA/°C max from 0 to 65°C ambient, 0.8 µA/°C max from -40 to 0°C ambient. Note: Analog output drift is separate from input drift.
Isolated Transmitter Power Supply Terminals I+ & R: 24 VDC ± 10%. Isolated from the input at >500 V. May be used to power the 4-20 mA output or other devices. All models @ 25 mA max.
External Loop Power Supply 35 VDC maximum
Output Loop Resistance
Power supply Minimum Maximum
24 VDC 10Ω 700Ω
35 VDC (external) 100Ω 1200Ω
Serial Communications
Compatability EIA-485
Connectors Removable screw terminal connector
Max Distance 3,937′ (1,200 m) max
Status Indication Separate LEDs for Power (P), Transmit (TX), and Receive (RX)
Protocol Modbus® RTU
Meter Address/Slave ID 1 – 247
Baud Rate 300 – 19,200 bps
Transmit Time Delay Programmable between 0 and 199 ms or transmitter always on for RS-422 communication
Data 8 bit (1 start bit, 1 or 2 stop bits)
Parity Even, odd, or none with 1 or 2 stop bits
Byte-to-Byte Timeout 0.01 – 2.54 second
Turn Around Delay Less than 2 ms (fixed)
Digital Inputs and Outputs
Channels 4 digital inputs & 4 digital outputs per module
System One expansion module may be added for a total of 8 inputs & 8 outputs Note: The jumper located between the RJ45 connectors must be removed on the expansion module.
Digital Input Logic: High 3 to 5 VDC
Digital Input Logic: Low 0 to 1.25 VDC
Digital Output Logic: High 3.1 to 3.3 VDC
Digital Output Logic: Low 0 to 0.4 VDC
Source Current 10 mA maximum output current
Sink Current 1.5 mA minimum input current
+5 V Terminal To be used as pull-up for digital inputs only. Connect normally open pushbuttons across +5 V & DI 1-4. Warning: DO NOT use +5 V terminal (pin 1) to power external devices.
Function Assignment The on-board digital inputs (1-4) are designed to mimic the behavior of the front panel buttons (Menu, F1, F2, & F3). If you wish to change their behavior, re-assign F1-F3 to the desired function, then change the corresponding digital input to match.
4-Relay Expansion Module
Relays Four Form A (SPST) rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (approx. 50 W) @125/250 VAC for inductive loads.
Product Ratings and Approvals
FM Enclosure Type 4X; IP66 Class I, Division 1, Groups B, C, D; Class II, Division 1, Groups E, F, G; Class III, Division 1, T5/T6 Class I, Zone 1, AEx d, IIC Gb T5/T6 Zone 21, AEx tb IIIC T90°C; Ta -40°C to +65°C T6 Ta = -40°C to +60°C; T5 Ta = -40°C to +65°C Certificate Number: 3047283
CSA Class I, Division 1, Groups B, C, D; Class II, Division 1, Groups E, F, G; Class III, Division 1 Class I Zone 1 Ex d IIC Zone 21 Ex tb IIIC T90°C -40°C -40°C Enclosure Type 4X & IP66 Certificate Number: 2531731
ATEX II 2 G D Ex d IIC T* Gb Ex tb IIIC T90°C Db IP68 Ta = -40°C to +*°C *T6 = -40°C to +60°C *T5 = -40°C to +65°C Certificate number: Sira 12ATEX1182
IECEx Ex d IIC T* Gb Ex tb IIIC T90°C Db IP68 Ta = -40°C to +*°C *T6 = -40°C to +60°C *T5 = -40°C to +65°C Certificate Number: IECEx SIR 12.0073