New Product
Ozone (Ambient) / Chemical & Petrochemical / Pharma / Water & Waste Water
Model 205 Dual Beam Ozone Monitor High
Ozone (Industrial) / Chemical & Petrochemical / Pharma / Water & Waste Water
106-MH Ozone MonitorTM (Industrial)
Ozone (Industrial) / Automotive & Manufacturing / Chemical & Petrochemical / Dairy / Food & Beverage / Lab & Gas / Pharma / Plastics / Power & Steam
106-HIndustrial Ozone MonitorTM
Fluke 1507 Insulation Resistance Tester, 50 to 1000 V
Features
- Rugged, compact advanced insulation resistance tester for electrical contractors and industrial and commercial electricians
- Automatically calculates polarization index and dielectric absorption ratio
- Makes repetitive tests simple and easy with a compare (pass/fail) function
- Offers multiple insulation test voltages: 50, 100, 250, 500, and 1000 V
- Performs insulation tests from 0.01 MΩ to 2.0 GΩ
- Includes live circuit detection to prevent insulation test if voltage >30 V is detected
Fluke 1507 Offers
Ideal for advanced industrial and electrical insulation testing, this insulation tester comes in a compact design and features versatility. Additionally, the multiple test voltages facilitate the tool for many troubleshooting, commissioning, and preventative maintenance applications.
Take advantage of the full feature set to easily and quickly perform advanced insulation resistance testing. Its handy size and lightweight make it easy to pack and use. Additional features, like the remote probe, save both time and money, especially when performing repetitive tests.
Specifications & Spare Parts
Fluke 1507 Specifications
| AC/DC Voltage Specifications | |
| Range | 600.0 V |
| Resolution | 0.1 V |
| Accuracy | 50 Hz to 400 Hz: ±(2% of rdg + 3 digits) |
| Input Impedance | 3 MΩ (nominal), < 100 pF |
| Common Mode Rejection Ratio (1 kΩ unbalanced) | >60 dB at DC, 50 or 60 Hz |
| Overload Protection | 600 V RMS or DC |
| Earth Bond Resistance Specifications | |
| Range | 20.00 Ω to 20.00 kΩ |
| Resolution | 0.01 Ω to 0.01 kΩ |
| Accuracy | ±(1.5% + 3 digits) |
| Overload Protection | 2 V RMS or DC |
| Open Circuit Test Voltage | >4.0 V, <8 V |
| Short Circuit Current | >200.0 mA |
| Insulation Specifications | |
| Measurement Range | 0.01 MΩ to 10 GΩ |
| Test Voltage | 50, 100, 250, 500, 1000 V |
| Test Voltage Accuracy | +20%, -0% |
| Short Circuit Current | 1 mA nominal |
| Auto Discharge | Discharge time <0.5 second for C = 1 µF or less |
| Live Circuit Indicator | Inhibit test if terminal voltage >30 V prior to initialization of test |
| Maximum Capacitive Load | Operable with up to 1 µF load |
| Live Circuit Detection | Inhibit test if terminal voltage > 30 V prior to initialization of test |
| Maximum Capacitive Load | Operable with up to 1 µF load |
| Measure Accuracy | 50 V: ±(3% + 5) 100 V: ±(3% + 5) 250 V: ±(3% + 5) 500 V: ±(3% + 5) 1000 V: ±(3% + 5) to 2000 MΩ, ±(10% + 3) above 2000 MΩ |