New Product

IO-8TCS-E

Features

  •  Modbus TCP Modules for Data Acquisition and Control Systems
  • Extremely cost-effective modules for industrial measurement and monitoring applications
  • A wide range of modules for various digital and analog inputs and outputs
  • Wide range of baud rates available in Modbus RTU modules

Get a quote

These Remote I/O Modules are designed for Ethernet Modbus TCP communication, ideal for data acquisition and control systems.

  • High Reliability: Ensures dependable performance in industrial environments.
  • Ease of Installation and Maintenance: Simplifies setup and reduces downtime for maintenance.
  • Cost-Effective Solution: Ideal for industrial measurement and monitoring applications.
  • Seamless Integration: Can be easily added to existing Ethernet Modbus networks.
  • Versatile Selection: Various types of I/O Modules are available to meet user-specific requirements.
  • LED Indicators: Provides clear status monitoring for digital inputs/outputs and fault diagnostics.
  • Interchannel Isolation: Special modules offer isolation between channels for added safety and performance.
  • Modbus TCP Protocol: Modules feature an Ethernet interface supporting the Modbus TCP protocol.

Specifications & Spare Parts

General Specification
Parameters Modbus TCP IO Modules
Interface Ethernet Modbus TCP
Communication Speed 10/ 100 MBPS
Operating Temperature -10℃ to 50℃
Storage Temperature -40℃ to 85℃
Humidity Up to 95% Non-condensing
Mounting DIN Rail
Weight 105 grams
Dimensions( W*H*D) 23*109*98 mm
Approval Standard Safety IEC950
Connectors EMC IEC 61000-4-2-A1 Level2, IEC 61000-4-3-A1 Level2, IEC 61000-4-4 Level3, CISPR 11:1997-A1, EN55011:1998 Group1 Class A
Input 18 Way screw connector on front
Communication RJ45 on topside of the unit
Logic Power 4 Pin Connector on bottom side of unit

 

IO-8TCS-E
Type of Input Thermocouple. mV
No. of Channels 8
Power Supply Logic Supply Voltage 12 to 24 VDC
Logic Supply Current 105mA @ 12 V / 54mA @ 24V
Field Supply Voltage N.A.
Field Supply Current N.A.
Voltage Input Range 0 to 50mV, ± 100mV
RTD Type N.A.
Thermocouple Type J, K, E, T, N, B, S, R, C, D, G
Cold Junction CJC Error: ±0.5°C Typically After 30 Minutes warm up time.
Burnout Detection Yes
Accuracy 32 Bits
Frequency ± 0.05% FSR
Resolution 0.1°C
Sampling Rate 37 Samples / Minute
Isolation between Channels 350 V Peak
Isolation between Field and Logic 1500 VRMS
Drift 100 ppm/°C