New Product

PD6210 ProVu Analog Input Batch Controller

Get a quote

Related Products

The ProVu PD6210 is an 1/8 DIN analog input (4-20 mA, 0-5 V, 1-5 V, etc.) digital batch controller specifically designed for single and multi-stage batching applications. It provides excellent but simple batch control capabilities with features such as preclose relays and automatic overrun correction for more accurate batches and intuitive front panel buttons for simple operation and menu navigation. The preclose deactivates a specific relay on the batch controller before the batch is finished in order to allow slower fill rates and increased accuracy. Automatic overrun correction keeps the batch size accurate over time and with system wear. With expansion module relays, up to eight-stage batching is possible; each additional stage-batching relay has an individually programmable preclose amount. Like all ProVu meters, the PD6210 batcher includes UL/C-UL listing and CE marking, a NEMA 4X front, and AC or DC power options.

Features

  • 0-20 mA, 4-20 mA, 0-5 V, 1-5 V, ±10 V Inputs
  • Start/Pause/Stop, Change Batch with Front Buttons
  • Display Batch Total, Rate, Grand Total, Count or Preset
  • Single or Multi-Stage Batch Control (Up to 8 Relays)
  • Automatic Overrun Correction
  • Rate in Units per Second, Minute, Hour, or Day
  • Automatic or Manual Batch Control
  • Low or High Flow Alarms while Batching
  • 9-Digit Grand Total with Overflow Feature
  • Count Up or Down with Each Batch
  • Optional SunBright Display Models for Outdoor Applications
  • Onboard USB and MeterView® Pro Programming Software

Specifications & Spare Parts

General Specifications

Display Upper: 0.60″ (15 mm), Lower: 0.46″ (12 mm), Both are 6 digits (-99999 to 999999), red LEDs, lead zero blanking.
Default Display Assignment Upper: batch total, Lower: rate (can be switched to grand total, batch count, or preset).
Custom Display Assignment Rate, total, grand total, batch count, preset, set points, units, alternating R & T, alternating R & GT.
Display Intensity Eight user-selectable intensity levels.
Operating Methods Programmable front panel buttons, digital inputs, PC and MeterView Pro software, and Modbus registers.
Non-Volatile Memory All settings stored for a minimum of ten years if power is lost.
Max/Min Display Max (Peak) / Min (Valley) readings stored until reset.
Power Options 85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or 12-24 VDC ± 10%, 15 W max.
Fuse UL Recognized, 5 A max, slow blow; up to 6 batch controllers can share one fuse.
Environmental Operating temperature: -40 to 65°C; Storage temperature: -40 to 85°C; Relative humidity: 0 to 90% non-condensing.
Enclosure 1/8 DIN, high impact plastic, UL 94V-0, black.
Dimensions 4.68″ x 2.45″ x 5.64″ (119 mm x 62 mm x 143 mm) (W x H x D).
Weight 9.5 oz. (269 g)

PD6210 Analog Input

Inputs Field selectable: 0-20, 4-20 mA, ±10 VDC (0-5, 1-5, 0-10 V), Modbus PV (Slave).
Accuracy ±0.03% of calibrated span ±1 count.
Temperature Drift 0.005% of calibrated span/°C max from 0 to 65°C ambient.
Programmable Exponent 1.0001 to 2.9999.
Low-Flow Cutoff 0-999999 (0 disables cutoff function).
Calibration Range 4-20 mA: 0.15 mA, ±10 V: 0.10 V.

PD6310 Pulse Input

Inputs Field selectable: Pulse or square wave 0-5 V, 0-12 V, 0-24 V @ 30 kHz; Modbus PV (Slave).
Accuracy ±0.03% of calibrated span ±1 count.
Low Gate 0.1-99.9 seconds.
High Gate 2.0-999.9 seconds.

Batch Controller

Rate Display Indication 0 to 999999, lead zero blanking. “R” LED illuminates while displaying rate.
Batch Preset 0.00001 to 999,999 based on batch total decimal point.
Automatic Batch Restart Delay 00000.1 to 999.9 seconds.
Grand Total Reset Via front panel button, external contact closure, serial communications.
Non-Resettable Grand Total Programmed as non-resettable by entering password “050873”.

Relays

Rating 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load.
Relay Assignment Assigned to batch control, sampling, rate, or grand total alarms.

Isolated 4-20 mA Transmitter Output

Output Source Rate/process, total, grand total, max, min, set points 1-8, Modbus input.
Accuracy ±0.1% FS ±0.004 mA.
External Loop Power Supply 35 VDC maximum.

Serial Communications

Protocol Modbus® RTU.
Baud Rate 300 – 19,200 bps.
Byte-to-Byte Timeout 0.01 – 2.54 seconds.

Digital I/O Expansion Module

Channels 4 digital inputs & 4 digital outputs per module.
System Up to 2 modules for a total of 8 inputs & 8 outputs.

4-Relay Expansion Module

Relays Four Form A (SPST) rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (50 watts).