PD8-6310 ProtEX- MAX Explosion-Proof Pulse Input Batch Controller

 

Get a quote

The ProtEX-MAX™ PD8-6310 offers all the functionality of the ProVu PD6310 as a fully FM, CSA, ATEX, and IECEx approved explosion-proof product. It is a pulse input (NPN, PNP, TTL, switch contact, sine wave, etc.) digital batch controller specifically designed for single and multi-stage batching applications. It provides excellent but simple batch control capabilities with features such as preclose relays and automatic overrun correction for more accurate batches and convenient SafeTouch® through-glass buttons for simple operation and menu navigation without having to remove the cover. The preclose deactivates a specific relay before the batch is finished in order to allow slower fill rates and increased accuracy. Automatic overrun correction keeps the batch size accurate over time and with system wear. The PD8-6310 includes a 24 VDC power supply to drive the flowmeter and can be equipped with up to four internal relays and a 4-20 mA analog output.

Quick Overview

  • Input: Pulse, open collector, NPN, PNP, TTL, switch contact, sine wave (coil), square wave; Modbus PV (slave)
  • Display: Dual-line 6-digit, 0.60″ (15 mm) & 0.46″ (12 mm)
  • Case: Smooth die-cast aluminum explosion-proof
  • Power: 85-265 VAC or 12-24 VDC option
  • Operating Temperature: -40 to 65°C

Features

  • SunBright Display Standard
  • Start, batch, & stop with pause front panel buttons
  • Display batch total + rate, grand total, batch count or preset
  • Single or multi-stage batching with up to 8 relays
  • Automatic overflow correction
  • Manual control or automatic batching
  • SafeTouch® through-glass button programming
  • Modbus RS-485 serial communications
  • Flanges for wall or pipe mounting
  • Isolated 24 VDC @ 25 mA transmitter power supply
  • Total can count up or down
  • Onboard USB and MeterView® Pro programming software

Specifications & Spare Parts

General

Display Upper display: 0.60″ (15 mm) high. Lower display: 0.46″ (12 mm) high. Both are 6 digits (-99999 to 999999), red LEDs.
Default Display Assignment The upper display shows batch total. The lower display shows rate with alternating units, and can be switched to show grand total, batch count, or preset with the STOP key.
Custom Display Assignment The upper and lower displays may be assigned to rate, total, grand total, batch count, preset, set points, units (lower display only), alternating R & T, R & GT, preset & rate, max & min, or a Modbus display register. Any rate/total/grand total display may be programmed to alternate with a custom unit or tag.
Alternating Display Displays alternate every 10 seconds when display is selected or the batch is paused.
Display Intensity Eight user selectable intensity levels
Display Update Rate 5/second (200 ms)
Overrange Display flashes 999999
Underrange Display flashes -99999
Programming Methods Four through-glass SafeTouch buttons, four mechanical buttons behind glass, digital inputs, PC and MeterView Pro software, or Modbus registers.
F4 Digital Input Contacts 3.3 VDC on contact. Connect normally open contacts across F4 to COM.
F4 Digital Input Logic Levels Logic High: 3 to 5 VDC; Logic Low: 0 to 1.25 VDC
Noise Filter Programmable from 2 to 199 (0 will disable filter)
Filter Bypass Programmable from 0.1 to 99.9% of calibrated span.
Recalibration Recommended at least every 12 months.
Max/Min Display Max (Peak) / min (Valley) readings reached by the process are stored until reset by the user or until power is cycled.
Password Three programmable passwords restrict modification of programmed settings and two prevent resetting the totals.
Non-Volatile Memory All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
Power Options 85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max, or optional model with 12-24 VDC ±10%, 15 W max.
Fuse Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 controllers may share one 5 A fuse.
Isolated Transmitter Power Supply Terminals P+ & P-: 24 VDC ± 10%. Isolated from the input at >500 V. Jumper selectable for 24, 10, or 5 VDC supply (internal jumper J4). All models transmitter supply rated @ 25mA max.
Normal Rejection Mode Greater than 60 dB at 50/60 Hz
Isolation 4 kV input/output-to-power line. 500 V input-to-output or output-to-P+ supply.
Overvoltage Category Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
Environmental T6 Class operating temperature range Ta = -40 to 60°C
T5 Class operating temperature range Ta = -40 to 65°C
Max Power Dissipation Maximum power dissipation limited to 15.1 W. See PD8 instruction manual for additional details.
Connections Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters.
Enclosure Explosion-proof die cast aluminum with glass window, corrosion resistant epoxy coating, color: blue. NEMA 4X, 7, & 9, IP68. Default conduit connections: Four ¾” NPT threaded conduit openings and two ¾” NPT metal conduit plugs with 12 mm hex key fitting installed. Additional conduit opening configurations may be available; verify quantity and sizes on specific device labeling during installation.
Mounting Four slotted flanges for wall mounting or NPS 1½” to 2½” or DN 40 to 65 mm pipe mounting
Dimensions 6.42″ x 7.97″ x 8.47″ (W x H x D) (163 mm x 202 mm x 215 mm)
Weight 16.0 lbs (7.26 kg)
Warranty 3 years parts & labor
USB Connection Compatibility: USB 2.0 Standard, Compliant
Connector Type: Micro-B receptacle
Cable: USB A Male to Micro-B Cable
Driver: Windows 98/SE, ME, 2000, Server 2003/2008, XP 32/64-Bit, Vista 32/64-Bit, Windows 7 32/64-Bit, Windows 10 32/64-Bit
Power: USB Port

Pulse Input

Inputs Field selectable: Pulse or square wave 0-5 V, 0-12 V, or 0-24 V @ 30 kHz; TTL; open collector 4.7 kΩ pull-up to 5 V @ 30 kHz; NPN or PNP transistor, switch contact 4.7 kΩ pull-up to 5 V @ 40 Hz; coil (sine wave) 40 mVp-p min @ 10 kHz; Modbus PV (Slave)
Low Voltage Mag Pickup (Isolated) Sensitivity: 40 mVp-p to 8 Vp-p
Minimum Input Frequency 0.001 Hz – Minimum frequency is dependent on high gate setting.
Maximum Input Frequency 30,000 Hz (10,000 for Low Voltage Mag Pickup)
Input Impedance Pulse input: Greater than 300 kΩ @ 1 kHz. Open collector/switch input: 4.7 kΩ pull-up to 5 V.
Accuracy ±0.03% of calibrated span ±1 count
Display Update Rate Total: 10/sec, Rate: 10/sec to 1/1000 sec
Temperature Drift Rate display is not affected by changes in temperature.
Multi-Point Linearization 2 to 32 points
Low-Flow Cutoff 0-999999 (0 disables cutoff function)
Decimal Point Up to five decimal places or none: d.ddddd, dd.dddd, ddd.ddd, dddd.dd, ddddd.d, or dddddd.
Calibration May be calibrated using K-factor, scale using internal calibration, or calibrate by applying an external calibration signal.
K-Factor Field programmable K-factor converts input pulses to rate in engineering units. May be programmed from 0.00001 to 999,999 pulses/unit.
Calibration Range Input 1 signal may be set anywhere in the range of the controller; input 2 signal may be set anywhere above setting.
Filter Programmable contact de-bounce filter, 40 to 999 Hz maximum input frequency allowed with low speed filter.
Time Base Second, minute, hour, or day
Low Gate 0.1-99.9 seconds; this function determines how often the incoming pulses are calculated and the rate display is updated.
High Gate 2.0-999.9 seconds; this function determines how long to wait for pulses before the display goes to zero. This function is used to display slow pulse rates.

Pulse Input (continued)

Note: The combination of the low and high gate functions makes it possible to have a fast display update for fast pulse rates while displaying slow pulse rates, if needed. For example: If the low gate is set to 1.0 second and the high gate to 999.9 seconds, with a fast pulse rate the display is updated every second; with a slow pulse rate, the controller is capable of waiting up to 999.9 seconds before calculating the rate, making it possible to display a very slow rate down to 1 pulse/999.9 second (0.001 pulse/second).

Batch Controller

Rate Display Indication 0 to 999999, lead zero blanking. “R” LED illuminates while displaying rate.
Total Displays & Grand Total Overflow 0 to 999,999; automatic lead zero blanking. “T” LED is illuminated while displaying batch total and “GT” for grand total. Up to 999,999,999 with total-overflow feature. “oF in 7-Segment Font” is displayed to the left of grand total overflow and Up Arrow LED is illuminated.
Batch Total Decimal Point Up to five decimal places or none: d.ddddd, dd.dddd, ddd.ddd, dddd.dd, ddddd.d, or dddddd. Total decimal point is independent of rate decimal point.
Totalizer Calculates total based on rate and field programmable multiplier to display total in engineering units. Time base must be selected according to the time units in which the rate is displayed.
Total Conversion Factor 0.00001 to 999,999
Batch Preset 0.00001 to 999,999 based on batch total decimal point.
Automatic Batch Restart Delay 00000.1 to 999.9 seconds. The batch will automatically restart after completion of the last batch.
Grand Total Rollover Totalizer rolls over when display exceeds 999,999,999. Relay status reflects the display value.
Grand Total Alarms Up to seven, user selectable under Setup menu. Any set point can be assigned to grand total and may be programmed anywhere in the range of the controller for grand total alarm indication. Note that Relay 1 should always be assigned to batch control (total).
Grand Total Reset Via front panel button, external contact closure on digital inputs, automatically via user selectable preset value and time delay, or through serial communications.
Grand Total Reset Password A grand total password may be entered to prevent resetting the grand total from the front panel.
Non-Resettable Grand Total The grand total can be programmed as a non-resettable total by entering the password “050873”. Caution: Once the Grand Total has been programmed as “non-resettable” the feature cannot be disabled.

Relays

Rating 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (≈ 50 W) @ 125/250 VAC for inductive loads.
Noise Suppression Noise suppression is recommended for each relay contact switching inductive loads.
Relay Assignment Relays may be assigned to batch control, sampling, rate, or grand total alarms.
Preclose 0-100% of batch size, individually user programmable for each additional batch control relay beyond the first.
Alarm Deadband 0-100% of span, user programmable
High or Low Alarm User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turned off).
Batching Relay Operation Single or (2 to 8) multi-relay batching with optional preclose for multi-stage operation. Each additional relay may be programmed with an individual preclose value.
Alarm Relay Operation Automatic (non-latching), latching (requires manual acknowledge), sampling (based on rate or grand total), pump alternation control (2 to 8 relays), off (disable unused relays), and manual on/off control mode. Alarms are active only when the batch is running.
Alarm Relay Reset User selectable via front buttons, digital inputs, or PC:

  1. Automatic reset only (non-latching), when input passes the reset point or total is reset to zero.
  2. Manual reset only, when batch is stopped (latching).
  3. Manual reset only after alarm condition has cleared (latching)

Note: Front panel button or digital input may be assigned to acknowledge relays programmed for manual reset. This replaces one of the standard batch control function keys. Only the PAUSE/STOP key function is possible during a batch process, so manual reset may only be done when the controller is in STOP mode.

Deadband 0-100% of span, user programmable
Time Delay 0 to 999.9 seconds, on & off relay time delays. Programmable and independent for each relay.
Fail-Safe Operation Programmable and independent for each relay. Note: Relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state.
Auto Initialization When power is applied, relays will reflect the state of the input. Alarms are active only when the batch is running.

Isolated 4-20 mA Transmitter Output

Output Source Rate/process, total, grand total, max, min, set points 1-8, manual control setting, or Modbus input
Scaling Range 1.000 to 23.000 mA for any display range
Calibration Factory calibrated: 4.000 to 20.000 = 4-20 mA output
Analog Output Programming 23.000 mA maximum for all parameters: Overrange, underrange, max, min, and break
Accuracy ±0.1% FS ±0.004 mA
Temperature Drift 0.4 µA/°C max from 0 to 65°C ambient, 0.8 µA/°C max from -40 to 0°C ambient
Isolated Transmitter Power Supply Terminals I+ & R: 24 VDC ± 10%. Isolated from the input at >500 V. May be used to power the 4-20 mA output or other devices. All models @ 25 mA max.
External Loop Power Supply 35 VDC maximum
Output Loop Resistance
Power supply Minimum Maximum
24 VDC 10 Ω 700 Ω
35 VDC (external) 100 Ω 1200 Ω

Serial Communications

Compatibility EIA-485
Connectors Removable screw terminal connector
Max Distance 3,937′ (1,200 m) max
Status Indication Separate LEDs for Power (P), Transmit (TX), and Receive (RX)
Protocol Modbus® RTU
Controller Address/Slave ID 1 – 247
Baud Rate 300 – 19,200 bps
Transmit Time Delay Programmable between 0 and 199 ms or transmitter always on for RS-422 communication
Data 8 bit (1 start bit, 1 or 2 stop bits)
Parity Even, odd, or none with 1 or 2 stop bits
Byte-to-Byte Timeout 0.01 – 2.54 seconds
Turn Around Delay Less than 2 ms (fixed)

Note: Refer to the PD6000/PD7000 Modbus Register Tables located in the documentation section of this page.

Digital Inputs and Outputs

Channels 4 digital inputs & 4 digital outputs per module
System One expansion module may be added for a total of 8 inputs & 8 outputs
Note: The jumper located between the RJ45 connectors must be removed on the expansion module.
Digital Input Logic: High 3 to 5 VDC
Digital Input Logic: Low 0 to 1.25 VDC
Digital Output Logic: High 3.1 to 3.3 VDC
Digital Output Logic: Low 0 to 0.4 VDC
Source Current 10 mA maximum output current
Sink Current 1.5 mA minimum input current
+5 V Terminal To be used as pull-up for digital inputs only. Connect normally open pushbuttons across +5 V & DI 1-4. Warning: DO NOT use +5 V terminal (pin 1) to power external devices.
Function Assignment The on-board digital inputs (1-4) are designed to mimic the behavior of the front panel buttons (Menu, F1, F2, & F3). If you wish to change their behavior, re-assign F1-F3 to the desired function, then change the corresponding digital input to match.

4-Relay Expansion Module

Relays Four Form A (SPST) rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (. 50 watts) @ 125/250 VAC for inductive loads.

Product Ratings and Approvals

FM Enclosure Type 4X; IP66
Class I, Division 1, Groups B, C, D
Class II, Division 1, Groups E, F, G
Class III, Division 1, T5/T6
Class I, Zone 1, AEx d, IIC Gb T5/T6
Zone 21, AEx tb IIIC T90°C; Ta -40°C to +65°C
T6 Ta = -40°C to +60°C; T5 Ta = -40°C to +65°C
Certificate Number: 3047283
CSA Class I, Division 1, Groups B, C, D
Class II, Division 1, Groups E, F, G
Class III, Division 1
Class I Zone 1 Ex d IIC
Zone 21 Ex tb IIIC T90°C
-40°C < Tamb. < +60° C; Temperature Code T6
-40°C < Tamb. < +65° C; Temperature Code T5
Enclosure Type 4X & IP66
Certificate Number: 2531731
ATEX II 2 G D    Ex d IIC T* Gb
Ex tb IIIC T90°C Db IP68
Ta = -40°C to +*°C
*T6 = -40°C to +60°C
*T5 = -40°C to +65°C
Certificate number: Sira 12ATEX1182
IECEx Ex d IIC T* Gb
Ex tb IIIC T90°C Db IP68
Ta = -40°C to +*°C
*T6 = -40°C to +60°C
*T5 = -40°C to +65°C
Certificate Number: IECEx SIR 12.0073