New Product

D8 Digital I/O DIN Rail Mount Module With 6 Inputs And 2 Outputs

D8 Digital I/O DIN rail mount module with 6 inputs and 2 outputs

Get a quote

Related Products

To increase the signal capabilities of control systems this unit is provided with:

  • Compact dimensions: 22.5 mm width, 99 mm length
  • 6 Digital inputs and 2 Digital outputs
  • 2 Inputs may be configured for frequency signals
  • Outputs may generate PWM signals
  • Power supply and RS485 communication on side bus.
  • Withdrawable electronic, configuration and parameters back-up for easy replacement and maintenance

Specifications & Spare Parts

Specifications
Process inputs 6 configurable digital inputs
– NPN
– TTL
– Free VoltageFrequency input (only DI1 and DI2)
Configurable range: 0.1…10kHz
Process outputs 2 Digital outputs

OUT1
– RELAY SPST-NO, 2A (250VAC)
– TRIAC 1A 250 VAC
– SSR Drive 0…5Vdc, ±20%, 30 mA Max

OUT2
– RELAY SPST-NO, 2A (250VAC)
– TRIAC 1A 250 VAC
– SSR Drive 0…5Vdc, ±20%, 30 mA Max

Power supply 24VDC/VAC
Transmitter power supply: 18 Vdc ±20%, 30 mA Max
Functions – NOT: Polarity change
– TOGGLE: Bistable with rising front change (type T)
– FLIP-FLOP: Bistable with:
Status 1 at S signal rising front
Status 0 at R signal rising front (type SR)
– HOLD: Output status freeze
– PWM Output with:
Adjustable frequency (0.1… 10 kHz)
Adjustable duty cycle (0… 100%)
– Configuration and parameters back-up and automatic restore (with DX master)
Communication and programming Interfaces
– RS 485 port with ModBus RTU and J-bus (slave) protocolsProgramming/configuration tools
– Configuration software available for PC
Installation Mounting method: DIN rail mount
Case dimensions: 22.5 x 99 mm, depth 114.5 mm
Connections Communication ports
– RS485 on male and female side bus connectionSignals connection
– 4 Extractable polarized 4 pole screw plugs, 2.5 mm²
– Withdrawable electronic without un-wiring signals, power supply, and communication bus
Connectable to – Deltadue Series
– SCADA for monitoring, traceability, and remote management
– DX and DY gateways for remote monitoring
Used for – Multiloop data acquisition and process control